Ejemplo n.º 1
0
Archivo: bv.c Proyecto: empeeoh/BACnet
void Binary_Value_Out_Of_Service_Set(
    uint32_t instance,
    bool oos_flag)
{
    unsigned index = 0;

    index = Binary_Value_Instance_To_Index(instance);
    if (index < MAX_BINARY_VALUES) {
        Out_Of_Service[index] = oos_flag;
    }
}
Ejemplo n.º 2
0
Archivo: bv.c Proyecto: empeeoh/BACnet
bool Binary_Value_Out_Of_Service(
    uint32_t instance)
{
    unsigned index = 0;
    bool oos_flag = false;

    index = Binary_Value_Instance_To_Index(instance);
    if (index < MAX_BINARY_VALUES) {
        oos_flag = Out_Of_Service[index];
    }

    return oos_flag;
}
Ejemplo n.º 3
0
static BACNET_BINARY_PV Binary_Value_Present_Value(
    uint32_t object_instance)
{
    BACNET_BINARY_PV value = RELINQUISH_DEFAULT;
    unsigned index = 0;
    unsigned i = 0;

    index = Binary_Value_Instance_To_Index(object_instance);
    if (index < MAX_BINARY_VALUES) {
        for (i = 0; i < BACNET_MAX_PRIORITY; i++) {
            if (Binary_Value_Level[index][i] != BINARY_NULL) {
                value = Binary_Value_Level[index][i];
                break;
            }
        }
    }

    return value;
}
Ejemplo n.º 4
0
/* returns true if successful */
bool Binary_Value_Write_Property(
    BACNET_WRITE_PROPERTY_DATA * wp_data)
{
    bool status = false;        /* return value */
    unsigned int object_index = 0;
    unsigned int priority = 0;
    BACNET_BINARY_PV level = BINARY_NULL;
    int len = 0;
    BACNET_APPLICATION_DATA_VALUE value;

    /* decode the some of the request */
    len =
        bacapp_decode_application_data(wp_data->application_data,
        wp_data->application_data_len, &value);
    /* FIXME: len < application_data_len: more data? */
    if (len < 0) {
        /* error while decoding - a value larger than we can handle */
        wp_data->error_class = ERROR_CLASS_PROPERTY;
        wp_data->error_code = ERROR_CODE_VALUE_OUT_OF_RANGE;
        return false;
    }
    /*  only array properties can have array options */
    if ((wp_data->object_property != PROP_PRIORITY_ARRAY) &&
        (wp_data->array_index != BACNET_ARRAY_ALL)) {
        wp_data->error_class = ERROR_CLASS_PROPERTY;
        wp_data->error_code = ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY;
        return false;
    }
    switch (wp_data->object_property) {
        case PROP_PRESENT_VALUE:
            if (value.tag == BACNET_APPLICATION_TAG_ENUMERATED) {
                priority = wp_data->priority;
                /* Command priority 6 is reserved for use by Minimum On/Off
                   algorithm and may not be used for other purposes in any
                   object. */
                if (priority && (priority <= BACNET_MAX_PRIORITY) &&
                    (priority != 6 /* reserved */ ) &&
                    (value.type.Enumerated <= MAX_BINARY_PV)) {
                    level = (BACNET_BINARY_PV) value.type.Enumerated;
                    object_index =
                        Binary_Value_Instance_To_Index
                        (wp_data->object_instance);
                    priority--;
                    Binary_Value_Level[object_index][priority] = level;
                    /* Note: you could set the physical output here if we
                       are the highest priority.
                       However, if Out of Service is TRUE, then don't set the
                       physical output.  This comment may apply to the
                       main loop (i.e. check out of service before changing output) */
                    status = true;
                } else if (priority == 6) {
                    /* Command priority 6 is reserved for use by Minimum On/Off
                       algorithm and may not be used for other purposes in any
                       object. */
                    wp_data->error_class = ERROR_CLASS_PROPERTY;
                    wp_data->error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
                } else {
                    wp_data->error_class = ERROR_CLASS_PROPERTY;
                    wp_data->error_code = ERROR_CODE_VALUE_OUT_OF_RANGE;
                }
            } else {
                status =
                    WPValidateArgType(&value, BACNET_APPLICATION_TAG_NULL,
                    &wp_data->error_class, &wp_data->error_code);
                if (status) {
                    level = BINARY_NULL;
                    object_index =
                        Binary_Value_Instance_To_Index
                        (wp_data->object_instance);
                    priority = wp_data->priority;
                    if (priority && (priority <= BACNET_MAX_PRIORITY)) {
                        priority--;
                        Binary_Value_Level[object_index][priority] = level;
                        /* Note: you could set the physical output here to the next
                           highest priority, or to the relinquish default if no
                           priorities are set.
                           However, if Out of Service is TRUE, then don't set the
                           physical output.  This comment may apply to the
                           main loop (i.e. check out of service before changing output) */
                    } else {
                        status = false;
                        wp_data->error_class = ERROR_CLASS_PROPERTY;
                        wp_data->error_code = ERROR_CODE_VALUE_OUT_OF_RANGE;
                    }
                }
            }
            break;
        case PROP_OUT_OF_SERVICE:
            status =
                WPValidateArgType(&value, BACNET_APPLICATION_TAG_BOOLEAN,
                &wp_data->error_class, &wp_data->error_code);
            if (status) {
                object_index =
                    Binary_Value_Instance_To_Index(wp_data->object_instance);
                Binary_Value_Out_Of_Service[object_index] = value.type.Boolean;
            }
            break;
        case PROP_OBJECT_IDENTIFIER:
        case PROP_OBJECT_NAME:
        case PROP_DESCRIPTION:
        case PROP_OBJECT_TYPE:
        case PROP_STATUS_FLAGS:
        case PROP_EVENT_STATE:
        case PROP_PRIORITY_ARRAY:
        case PROP_RELINQUISH_DEFAULT:
            wp_data->error_class = ERROR_CLASS_PROPERTY;
            wp_data->error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
            break;
        default:
            wp_data->error_class = ERROR_CLASS_PROPERTY;
            wp_data->error_code = ERROR_CODE_UNKNOWN_PROPERTY;
            break;
    }

    return status;
}
Ejemplo n.º 5
0
/* return apdu len, or BACNET_STATUS_ERROR on error */
int Binary_Value_Read_Property(
    BACNET_READ_PROPERTY_DATA * rpdata)
{
    int len = 0;
    int apdu_len = 0;   /* return value */
    BACNET_BIT_STRING bit_string;
    BACNET_CHARACTER_STRING char_string;
    BACNET_BINARY_PV present_value = BINARY_INACTIVE;
    unsigned object_index = 0;
    unsigned i = 0;
    bool state = false;
    uint8_t *apdu = NULL;

    if ((rpdata == NULL) || (rpdata->application_data == NULL) ||
        (rpdata->application_data_len == 0)) {
        return 0;
    }
    apdu = rpdata->application_data;
    switch (rpdata->object_property) {
        case PROP_OBJECT_IDENTIFIER:
            apdu_len =
                encode_application_object_id(&apdu[0], OBJECT_BINARY_VALUE,
                rpdata->object_instance);
            break;
            /* note: Name and Description don't have to be the same.
               You could make Description writable and different */
        case PROP_OBJECT_NAME:
        case PROP_DESCRIPTION:
            Binary_Value_Object_Name(rpdata->object_instance, &char_string);
            apdu_len =
                encode_application_character_string(&apdu[0], &char_string);
            break;
        case PROP_OBJECT_TYPE:
            apdu_len =
                encode_application_enumerated(&apdu[0], OBJECT_BINARY_VALUE);
            break;
        case PROP_PRESENT_VALUE:
            present_value =
                Binary_Value_Present_Value(rpdata->object_instance);
            apdu_len = encode_application_enumerated(&apdu[0], present_value);
            break;
        case PROP_STATUS_FLAGS:
            /* note: see the details in the standard on how to use these */
            bitstring_init(&bit_string);
            bitstring_set_bit(&bit_string, STATUS_FLAG_IN_ALARM, false);
            bitstring_set_bit(&bit_string, STATUS_FLAG_FAULT, false);
            bitstring_set_bit(&bit_string, STATUS_FLAG_OVERRIDDEN, false);
            state = Binary_Value_Out_Of_Service[object_index];
            bitstring_set_bit(&bit_string, STATUS_FLAG_OUT_OF_SERVICE, state);
            apdu_len = encode_application_bitstring(&apdu[0], &bit_string);
            break;
        case PROP_EVENT_STATE:
            /* note: see the details in the standard on how to use this */
            apdu_len =
                encode_application_enumerated(&apdu[0], EVENT_STATE_NORMAL);
            break;
        case PROP_OUT_OF_SERVICE:
            object_index =
                Binary_Value_Instance_To_Index(rpdata->object_instance);
            state = Binary_Value_Out_Of_Service[object_index];
            apdu_len = encode_application_boolean(&apdu[0], state);
            break;
        case PROP_PRIORITY_ARRAY:
            /* Array element zero is the number of elements in the array */
            if (rpdata->array_index == 0)
                apdu_len =
                    encode_application_unsigned(&apdu[0], BACNET_MAX_PRIORITY);
            /* if no index was specified, then try to encode the entire list */
            /* into one packet. */
            else if (rpdata->array_index == BACNET_ARRAY_ALL) {
                object_index =
                    Binary_Value_Instance_To_Index(rpdata->object_instance);
                for (i = 0; i < BACNET_MAX_PRIORITY; i++) {
                    /* FIXME: check if we have room before adding it to APDU */
                    if (Binary_Value_Level[object_index][i] == BINARY_NULL)
                        len = encode_application_null(&apdu[apdu_len]);
                    else {
                        present_value = Binary_Value_Level[object_index][i];
                        len =
                            encode_application_enumerated(&apdu[apdu_len],
                            present_value);
                    }
                    /* add it if we have room */
                    if ((apdu_len + len) < MAX_APDU)
                        apdu_len += len;
                    else {
                        rpdata->error_class = ERROR_CLASS_SERVICES;
                        rpdata->error_code = ERROR_CODE_NO_SPACE_FOR_OBJECT;
                        apdu_len = BACNET_STATUS_ERROR;
                        break;
                    }
                }
            } else {
                object_index =
                    Binary_Value_Instance_To_Index(rpdata->object_instance);
                if (rpdata->array_index <= BACNET_MAX_PRIORITY) {
                    if (Binary_Value_Level[object_index][rpdata->array_index]
                        == BINARY_NULL)
                        apdu_len = encode_application_null(&apdu[apdu_len]);
                    else {
                        present_value = Binary_Value_Level[object_index]
                            [rpdata->array_index];
                        apdu_len =
                            encode_application_enumerated(&apdu[apdu_len],
                            present_value);
                    }
                } else {
                    rpdata->error_class = ERROR_CLASS_PROPERTY;
                    rpdata->error_code = ERROR_CODE_INVALID_ARRAY_INDEX;
                    apdu_len = BACNET_STATUS_ERROR;
                }
            }
            break;
        case PROP_RELINQUISH_DEFAULT:
            present_value = RELINQUISH_DEFAULT;
            apdu_len = encode_application_enumerated(&apdu[0], present_value);
            break;
        default:
            rpdata->error_class = ERROR_CLASS_PROPERTY;
            rpdata->error_code = ERROR_CODE_UNKNOWN_PROPERTY;
            apdu_len = BACNET_STATUS_ERROR;
            break;
    }
    /*  only array properties can have array options */
    if ((apdu_len >= 0) && (rpdata->object_property != PROP_PRIORITY_ARRAY) &&
        (rpdata->array_index != BACNET_ARRAY_ALL)) {
        rpdata->error_class = ERROR_CLASS_PROPERTY;
        rpdata->error_code = ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY;
        apdu_len = BACNET_STATUS_ERROR;
    }

    return apdu_len;
}
Ejemplo n.º 6
0
/* returns true if successful */
bool Binary_Value_Write_Property(
    BACNET_WRITE_PROPERTY_DATA * wp_data,
    BACNET_ERROR_CLASS * error_class,
    BACNET_ERROR_CODE * error_code)
{
    bool status = false;        /* return value */
    unsigned int object_index = 0;
    int len = 0;
    BACNET_APPLICATION_DATA_VALUE value;

    if (!Binary_Value_Valid_Instance(wp_data->object_instance)) {
        *error_class = ERROR_CLASS_OBJECT;
        *error_code = ERROR_CODE_UNKNOWN_OBJECT;
        return false;
    }
    /* decode the some of the request */
    len =
        bacapp_decode_application_data(wp_data->application_data,
        wp_data->application_data_len, &value);
    /* FIXME: len < application_data_len: more data? */
    if (len < 0) {
        /* error while decoding - a value larger than we can handle */
        wp_data->error_class = ERROR_CLASS_PROPERTY;
        wp_data->error_code = ERROR_CODE_VALUE_OUT_OF_RANGE;
        return false;
    }
    switch (wp_data->object_property) {
        case PROP_PRESENT_VALUE:
            if (value.tag == BACNET_APPLICATION_TAG_ENUMERATED) {
                if ((value.type.Enumerated == BINARY_ACTIVE) ||
                    (value.type.Enumerated == BINARY_INACTIVE)) {
                    object_index =
                        Binary_Value_Instance_To_Index
                        (wp_data->object_instance);
                    /* NOTE: this Binary value has no priority array */
                    Present_Value[object_index] =
                        (BACNET_BINARY_PV) value.type.Enumerated;
                    /* Note: you could set the physical output here if we
                       are the highest priority.
                       However, if Out of Service is TRUE, then don't set the
                       physical output. */
                    if (Present_Value[0] == BINARY_ACTIVE) {
                        LED_GREEN_ON();
                    } else {
                        LED_GREEN_OFF();
                    }
                    status = true;
                } else {
                    *error_class = ERROR_CLASS_PROPERTY;
                    *error_code = ERROR_CODE_VALUE_OUT_OF_RANGE;
                }
            } else {
                *error_class = ERROR_CLASS_PROPERTY;
                *error_code = ERROR_CODE_INVALID_DATA_TYPE;
            }
            break;
#if 0
        case PROP_OUT_OF_SERVICE:
            if (value.tag == BACNET_APPLICATION_TAG_BOOLEAN) {
                object_index =
                    Binary_Value_Instance_To_Index(wp_data->object_instance);
                Binary_Value_Out_Of_Service[object_index] = value.type.Boolean;
                status = true;
            } else {
                *error_class = ERROR_CLASS_PROPERTY;
                *error_code = ERROR_CODE_INVALID_DATA_TYPE;
            }
            break;
#endif
        default:
            *error_class = ERROR_CLASS_PROPERTY;
            *error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
            break;
    }

    return status;
}